IITEMA   27339
INSTITUTO DE INVESTIGACIONES EN TECNOLOGIAS ENERGETICAS Y MATERIALES AVANZADOS
Unidad Ejecutora - UE
artículos
Título:
Decoupled digital control of a three-phase four-leg inverter to feed balanced and unbalanced loads Control digital desacoplado de inversores trifásicos de cuatro piernas para alimentar cargas equilibradas y desequilibradas
Autor/es:
OGGIER, E.; GARCÍA, G.; BOTTERÓN, F.; OGGIER, G.
Revista:
REVISTA IBEROAMERICANA DE AUTOMATICA E INFORMATICA INDUSTRIAL
Editorial:
COMITE ESPANOL AUTOMATICA CEA
Referencias:
Año: 2020 vol. 17 p. 306 - 317
ISSN:
1697-7912
Resumen:
This paper presents a digital control strategy for three-phase four-leg inverters to meet the requirements of international power quality standards for UPS, when balanced and unbalanced loads are feeding. The proposed control strategy is developed in the discrete-Time dq0-reference frame. It has an inner current loop to control the inductors currents and an outer voltage control loop. The analysis of this paper demonstrates that using conventional controllers, the voltages of d and q axes can be decoupled, into the whole operating range, which allows the outer voltage controllers to be designed as independent SISO systems, meeting the requirements of the transient and permanent regimes imposed by Standards. To improve the performance when the inverter feeds unbalanced loads, this paper proposes to use a Proportional-Resonant controller only in the inner loop of the axis 0, achieving a simple control strategy and, consequently with a low computational cost. Simulation and experimental results allow validating the proposed control strategy.