INVESTIGADORES
CABRAL Roberto JosÉ
congresos y reuniones científicas
Título:
Improvement of an Overhead distribution Feeder Performance Against Lightning Considering the Wire-Guard Protection and New Grounding Arrangements
Autor/es:
CABRAL, R.J.; GAZZANA, D.S.; LEBORGNE, R.C.; BRETAS, A.S.; DIAS, G.A.D.; TELLO, M.
Lugar:
Viena
Reunión:
Conferencia; 2012 International Conference on Lightning Protection (ICLP); 2012
Institución organizadora:
IEEE
Resumen:
This paper presents a study about the infl uence of the wire-guard as a protection system in overhead distribution line in comparison with unprotected topology against lightning. A real feeder was considered as a case study using ATP-EMTP soft ware. Practical aspects related to the modeling of a distribution line are presented. Simulation results show that the shielding confi guration ensures a protection signifi cantly better than the actual topology, around 10 times in terms of lightning peak current. Thus, the wire-guard can improve the immunity of distribution system against atmospheric discharges.